Chapter 7: Jury Facilities
Table 7.4 (continued)
Heating, Ventilating, and Air Conditioning (HVAC) and Lighting
HVAC
LIGHTING
TEMP
TYPE:
(degrees Fahrenheit)
HUMIDITY
I = Indirect
(degrees Celsius)
(Perc.)
D = Direct
CONTROL
S
W
S
W
GENERAL
LEVEL
SPACES
REMARKS
REMARKS
(FTC) (lx)
TRIAL JURY SUITE (cont'd)
(1) Outdoor
temperature equal
Trial Jury Room
74-76
70-74
45-55
25-35
20
8
60
D
Q
Q
Q
to ASHRAE 1%
(23.3-24.4)
(21.1-23.3)
(9.45)
fan to operate
(650)
design dry bulb and
(1)
(2)
(3)
(4)
only when room
coincident wet bulb.
is occupied
Service Unit
(2) Outdoor
temperature equal
to ASHRAE 99%
design dry bulb.
Video Equipment
(3) Outdoor air at
design
temperature.
Sworn Jury
45-55
25-35
8
80-85
50
D
Q
Custodian Station
(3)
(4)
(540)
(4) Outdoor
temperature is
GRAND JURY SUITE
ASHRAE 97.5%.
Entry Area
74-76
70-74
45-55
25-35
20
8
20-30
D
Q
(23.3-24.4)
(21.1-23.3)
(9.45)
(215-320)
(1)
(2)
(3)
(4)
Jurors' Toilets
Service Unit
20-30
D
Q
(215-320)
Security Work Station
45-55
25-35
8
80-85
40-60
D
Q
(3)
(4)
(430-650)
Witness Room
8
80-85
30-40
D
Q
(320-430)
Hearing Room
8
40-60
D
Q
Q
Q
fan to operate
(430-650)
only when room
is occupied
Video Equipment
Closet
12/19/97
7-17