LOCATION
EQUIPMENT/OUTLET(S)
NOTES
GRAND JURY (continued)
Other areas
Distributed convenience outlets, including provisions for cleaning/
GFI in toilet areas, per codes.
housekeeping.
JURY ASSEMBLY
Jury Assembly Room
Distributed convenience outlets. Provide outlets as required for
Computer and office equipment
video conferencing equipment, video monitors/VCR equipment,
(PC, monitor, printer) not in
security, sound-system, ALS and other equipment, based on antici-
FF&E budget.
pated locations. Provide outlets for use at carrels and tables for
jurors for personal use.
Jury Clerk Workstation(s)
One quadriplex receptacle (general use). Duplex outlet(s),
Computer and office equipment
two minimum, for PC, monitor, printer, FAX.
(PC, monitor, printer) not in
FF&E budget.
Other Area(s)
Distributed convenience outlets, including provisions for cleaning
equipment/motor loads.
LAW LIBRARY
Circulation Desk
Outlets for PC, other equipment. Distributed convenience outlets.
Public Waiting Areas
Distributed convenience outlets, including provisions for
cleaning/housekeeping.
Entry Control
Security equipment. Distributed convenience outlets, including
provisions for cleaning/housekeeping.
if/as required.
Staff Offices
One quadriplex receptacle (general use). Duplex outlet(s),
Computer and office equipment
two minimum (for PC, monitor, printer, FAX) per workstation.
(PC, monitor, printer) not in
FF&E budget.
Staff Work Areas
Distributed convenience outlets; quadriplex receptacle(s) for
Computer and office equipment
general purpose use. Additional outlet(s) for copier.
(PC, monitor, printer) not in
FF&E budget.
CALR Areas
Duplex outlet(s), two minimum (for PC, monitor, printer, FAX)
per workstation.
if/as required.
Carrel/Casual Seating Areas
Distributed convenience outlets. Provide outlets for use at carrels
and tables.
Conference/ Group Study/
Multiple outlets (as required) for sound, ALS, data, telecommunica-
Work Rooms
tion and video recording and presentation equipment. Duplex outlet
for Microfiche machine.
287
DESIGN
STANDARDS
FOR
U.S.
COURT
FAC I L IT I E S
9.7
Electrical Systems
Revised March 2005 PBS-P100