Chapter 6: Ancillary Facilities
Table 6.4 (continued)
Heating, Ventilating, and Air Conditioning (HVAC) and Lighting
HVAC
LIGHTING
TEMP
TYPE:
(degrees Fahrenheit)
HUMIDITY
I = Indirect
(degrees Celsius)
(Perc.)
D = Direct
CONTROL
S
W
S
W
GENERAL
LEVEL
SPACES
REMARKS
(FTC) (lx)
DISTRICT/BANKRUPTCY COURT
(1) Outdoor temperature
equal to ASHRAE 1%
Judges' Conference Room
74-76
70-74
45-55
25-35
20
8
80-85
60-75
D
design dry bulb and
Q
(23.3-
(21.1-
(3)
(4)
(9.45)
(650-
coincident wet bulb.
24.4) (1)
23.3) (2)
800)
(2) Outdoor temperature
equal to ASHRAE 99%
Conference/Robing Room
design dry bulb.
(3) Outdoor air at design
Service Unit
temperature.
(4) Outdoor temperature is
Attorney Conference/
45-
25-
8
80-85
50 (540)
D
D
Q
ASHRAE 97.5%.
Witness Waiting Room
55 (3)
35 (4)
Public Waiting Area
45-
25-
80-85
30 (320)
D
Q
55 (3)
35 (4)
News Media Room (optional)
45-
25-
80-85
50 (540)
D
Q
55 (3)
35 (4)
COURT REPORTER/RECORDER
Court Reporter/Recorder
74-76
70-74
45-
25-
20
80-85
50 (540)
D
Q
Office
(23.3-
(21.1-
55
35
(9.45)
24.4) (1)
23.3) (2)
(3)
(4)
Court Reporter/Recorder
Storage
Shared Work Room
45-
25-
80-85
D
Q
55 (3)
35 (4)
Transcriber/Typist
45-
25-
80-85
D
Q
Workstation
55 (3)
35 (4)
12/19/97
6-9