7.17 Emergency Power,
U.S. Court Facilities
For special fire protection and life safety requirements
Lighting and Exit Signage
for U.S. Courts facilities, refer to PBS-P100 Chapter 9 and
the U.S. Courts Design Guide.
Emergency and Standby Power Systems. Emergency and
U.S. Marshal Service
standby power shall meet the performance requirements
in NFPA 70, NFPA 110, and NFPA 111.
For special fire protection and life safety requirements
for U.S Marshal Service space, refer to the USMS
Emergency Lighting. Emergency lighting shall meet
Requirements and Specifications for Special Purpose and
the performance requirements in NFPA 101.
Support Space; Volumes I, II, and III.
Exit Signage. Exit signage shall be installed and meet
Land Port of Entry Facilities
the performance requirements in NFPA 101.
For special fire protection and life safety requirements
for Land Port of Entry Facilities, refer to the Land Port
of Entry Design Guide.
Child Care Centers
For special fire protection and life safety requirements
for Child Care Centers, refer to the GSA Child Care Center
Design Guide (PBS-P140).
Child Care Center
231
FIRE
PROTECTION
&
LIFE
SAFETY
7.17
Emergency Power, Lighting and Exit Signage
Revised March 2005 PBS-P100