DOE-2 Energy Modeling Summary - Office Building
Page 9 of 21
Computer Room
All year
Weekdays
All hours
AHU fans on
Weekends, Holidays All hours
AHU fans on
Mechanical
All year
Weekdays
6 a.m. - 8 p.m.
AHU fans on
8 p.m. - 6 a.m.
AHU fans off unless heating or cooling
required
Weekends, Holidays 8 p.m. - 6 a.m.
AHU fans off unless heating or cooling
required
Parking Area
All year
Weekdays
6 a.m. - 10 a.m.
AHU fans on
10 a.m. - 3 p.m.
AHU fans off
3 p.m. - 8 p.m.
AHU fans on
8 p.m. - 6 a.m.
AHU fans off
Weekends, Holidays All hours
AHU fans off
(The Parking Area fan schedule reflects carbon monoxide sensor controls.)
Ventilation Air Amounts
Requirements per ASHRAE 62-1999
General
20 cfm per person
0.05 cfm/ft2
Corridors
1.5 cfm/ft2
Parking
Ventilation Air Schedules
Ventilation air schedules follow the schedules described in Section B, Building Occupancy
Patterns. When no ventilation is required, 2% of the rated fan flow is assumed due to damper
leakage.
Efficiency
65% (combined fan and motor efficiency)
Static pressure drop
2 in. W.C.
Schedule
follows AHU fan schedule