DOE-2 Energy Modeling Summary - Office Building
Page 6 of 21
C.
LIGHTING AND MISCELLANEOUS EQUIPMENT LOADS
Lighting Schedules (power density):
Lighting Power Density:
C
1.1 W/ft2
Office
C
0.3 W/ft2
Office (Task)
C
0.75 W/ft2
Corridor
C
1.0 W/ft2
Mechanical
C
1.1 W/ft2
Security
C
0.2 W/ft2
Parking
General Office Areas:
Weekends
All Hours
5%
Weekdays
Midnight - 7am
5%
& Holidays
7am - 7pm
100%
7pm - Midnight
5%
General Office Areas - Task Lighting:
Weekends
All Hours
0%
Weekdays
Midnight - 7am
0%
& Holidays
7am - 8am
30%
8am - Noon
100%
Noon - 1pm
60%
1pm - 5pm
100%
5pm - Midnight
0%
Miscellaneous Electrical Equipment Schedules (power density):
General Office Areas (1.30 W/ft2), Core/Public Areas (0.5 W/ft2):
Weekdays
Midnight - 6am
10%
Weekends
All Hours
10%
6am - 7pm
100%
& Holidays
7pm - Midnight
10%
Computer Room (65 W/ft2):
All
Midnight - Midnight
100%
APPENDIX J - GSA LEED COST STUDY