Chapter 4: Courtrooms
Table 4.4 (continued)
Heating, Ventilating, and Air Conditioning (HVAC) and Lighting
HVAC
LIGHTING
TEMP
TYPE:
(degrees Fahrenheit)
HUMIDITY
I = Indirect
(degrees Celsius)
(Perc.)
D = Direct
CONTROL
S
W
S
W
LEVEL
SPACES
GENERAL REMARKS
(FTC) (lx)
COURTROOM USER STATIONS
(1) Outdoor temperature
equal to ASHRAE 1%
Jurors
40-75
I/D
D
I
design dry bulb and
(430-800)
coincident wet bulb.
Court Reporter/Recorder
40-75
I/D
D
I
(USDC/USBC)
(430-800)
(2) Outdoor temperature
equal to ASHRAE 99%
Attorney and Litigants
40-75
I/D
D
I
design dry bulb.
(430-800)
Attorney Waiting Area
40-75
I/D
D
I
(3) Outdoor air at design
(430-800)
temperature.
Law Clerk(s)
40-75
I/D
D
I
(4) Outdoor temperature is
(430-800)
ASHRAE 97.5%.
Bailiff (USCA)
40-75
I/D
D
I
Q
Q
(430-800)
(5)
(5) An emergency
"override" switch to restore
USMS Personnel
40-75
I/D
D
I
full brightness
(430-800)
instantaneously during a
Spectators
74-76
70-74
45-55
25-35
20
6-8/
85
25-
30-40
I/D
D
I
dimming sequence.
(23.3-24.4)
(21.1-23.3)
(9.45)
8-10
30
(320-430)
(1)
(2)
(3)
(4)
OTHER SPACES
Equipment Storage Room
30-40
D
I
Q
(320-430)
30-40
D
I
Q
(320-430)
Lectern
75
D
I
(800)
Exhibit Display
75
D
I
(USDC/USBC)
(800)
Soundlock
30
D
I
Q
(320)
Public/Attorney Coat Rack
12/19/97
4-33